Every cubic meter (m3) of room space Every perspn Every PC/printer/fax/copying machine Every coffee machine (major dispenser) |
0,04 KW 0,15 KW 0,20 KW 1,00 KW |
||
Example calculation Office of 10 by 4 meters and a standard ceiling height of 2,4 meters. 4 persons work here, each with a PC. A printer and fax are shared. |
|||
Room 10x4x2,4=96 m3 4 persons 4 PCs + 1 printer + 1 fax Total |
96 x 0,04 4 x 0,15 6 x 0,20
|
3,84 0,60 1,20 5,64 KW |
|
| The total needed capacity does not
need to handled by a single airco. Though more expensive, multiple
smaller airco's provide a more even (and comfortable) cooling distribution. Example : 1 airco of 5,6KW is more uneven than 3 of 1,9KW |
|||
| For a more extensive cooling calculation or special requirements, such as tents or industrial equipment, contact us. | |||